The 4-20mA output from the sensor can be used with the ADC-11, so long as it is not a current loop.
To turn the output into a voltage that the ADC-11 can read 0-2.5 volts the 120 Ohm resistor is placed between the gnd and the input.
This means that your sensor will have a Ouput Signal (+) and gnd cable. If this is not the case the signal will have to be signal conditioned first to turn it into a single ended voltage. If you are unsure of the type of output from the sensor contact the manufacturer.
If you use the ADC-11 terminal board, this will make it simple to make the shunt resistor.