Multiple Thermistor Temperature Logging

 
Post new topic   Reply to topic    Pico Technology Forum Index -> Pre-Sales Advice
Author Message
Mark Dorogi
Guest





PostPosted: Mon Dec 22, 2003 5:00 am    Post subject: Multiple Thermistor Temperature Logging Reply with quote

I am putting in a solar water heating system and would like to measure temperatures in a number of places. Typically these systems use 10kohm thermistors. The curve of resistance vs temperature for these standard sensors is commonly available.

Would it be possible to record temperatures from say 16 of these thermistors, every few seconds? What hardware would be necessary?
Back to top
ricardo
Moderator
Moderator


Joined: 07 May 2003
Posts: 98

PostPosted: Wed Dec 24, 2003 10:07 am    Post subject: Reply with quote

Hi,

You should be able to do this with an ADC-11 or ADC-16. There will be some simple signal conditioning involved so you can calculate the resistance by measuring the voltage. You will get a data sheet with the unit explaining how to do the signal conditioning to measure Temperature from Precision Thermistors.

Best Regards,

Ric
Back to top
Guest






PostPosted: Mon Feb 09, 2004 2:44 am    Post subject: Reply with quote

Now my solar hot water system is up and running and I am thinking again about logging some temperature data.

You mention simple signal conditioning. Can you explain a little? I assume some additional hardware is needed to turn the thermistor resistance value into a voltage (0 to 2.5V) that is then input into the ADC. Is this correct?
Back to top
markspencer
Site Admin
Site Admin


Joined: 07 May 2003
Posts: 607

PostPosted: Mon Feb 09, 2004 10:35 am    Post subject: Reply with quote

Hi,

The siganal conditioning will only need to be done if the thermister gives very small changes or if the voltage can go above the 2.5 volts for the unit. You would need to design you circuitry, so that the voltage is measured across the resistor. and therefore you can calculate the resistance change.

A look up table would be required to convert the voltage into a scaled value in temperature. The details of this would be provided by the thermisters data sheet.

Best regards,
Back to top
jmaril
Guest





PostPosted: Tue Feb 24, 2004 9:58 pm    Post subject: Re: Multiple Thermistor Temperature Logging + BACnet Reply with quote

Mark Dorogi wrote:
I am putting in a solar water heating system and would like to measure temperatures in a number of places. Typically these systems use 10kohm thermistors. The curve of resistance vs temperature for these standard sensors is commonly available.

Would it be possible to record temperatures from say 16 of these thermistors, every few seconds? What hardware would be necessary?


I have the same project.
Could you please tell me where you are in this business ?
What did you buy and made. I need to do the same.
--------------
Besides a solar heating system, it's also very useful to instrument and control any heating system of significant size:
- measuring temperature, and sometimes flow in primary and secondary hydraulic circuits;
- recording in real time gaz and water volume with reed contacts on counters;
- recording some quality parameters like pH, iron concentration...
ASHRAE, The American Society of Heating Refrigeration and Air-conditionning Engineers has defined the BACnet standard of such data communication.
I thinck I would like suggest PICO TECHNOLOGY enter this business and help his clients on this quite new and growing applications
Who can discuss with that with me ?